3

Alarms

Pre-event context, runbooks, and notification echo to customer engineering.

CRITICALALM-2026-0412-001· 22m ago

C₂H₂ rise on T2 — possible arcing in oil

Acetylene climbed from 0.4 ppm → 2.3 ppm over last 14 days. Duval Triangle zone shifted D1 → D2 (high-energy arcing).

Asset · SiteT2east-thistle
Open asset

Pre-event context · 15 minT2.dga.c2h2

Source · INSIDEVIEW 6.0 · Duval Triangle

Runbook

Acetylene rise · suspected arcing

C₂H₂ is the single strongest indicator of arcing in oil. Treat any rise above LDL as a priority investigation.

  1. Verify Duval Triangle zone shift from D1 → D2 via INSIDEVIEW 6.0.
  2. Cross-check with CO / CO₂ ratio to rule out cellulose involvement.
  3. Pull a lab sample within 24 hrs (Myrkos 2 if portable unit is on-site).
  4. Escalate to lead PE and schedule offline electrical testing in next planned outage.
  5. Notify customer engineering (read-only dashboard) via APG monitoring center.
Escalate · Tim Sabat (APG) → Yonan G. (O&M) → Doble: Nicholas Chiccarelli

Notification echo

SMSsent
APG ops · on-call
Emailsent
monitoring@apg + customer
Pushsent
APG mobile · responder
42 MVA, 69/34.5 kV Δ-Y

Command palette

Search assets, alarms, sites, and quick actions

APG Copilot
Hi — I'm your APG assistant. Ask me anything: "any critical alarms?", "draft a DGA report for T2", "what spares are behind their lead time?"

Powered by CopilotKit