APG MonitorFleet dashboard
2 critical3
Fleet
Live status across APG's substations and the RE&D power-quality fleet.
Streams
612
Live
Alarms
7
2 critical · 2 warn
Sites healthy
3/7
PM ≤ 30 d
9
Reorder
8
Responder SLA
2 hr
CriticalT2· 22m ago
C₂H₂ rise on T2 — possible arcing in oil
Acetylene climbed from 0.4 ppm → 2.3 ppm over last 14 days. Duval Triangle zone shifted D1 → D2 (high-energy arcing).
Fleet map
7 sites · 1 substation · 6 PQ · click a pin to drill in
Acetylene (C₂H₂)
warn 1 · alarm 35 ppm
Hydrogen (H₂)
warn 100 · alarm 500 ppm
CH₄
62.00 ppm
CO
210.00 ppm
Top-oil temp
58.00 °C
Winding hot-spot
74.00 °C
Sites
Substations first · PQ fleet below.
East Thistle
Menlo Digital
4801 East Thistle Landing Dr, Phoenix AZ 85044
69 / 34.5 kV · 3× 42 MVA
Streams312
NERC-WECCData CenterTier 1
Kingston Solar PQ
Kingston Solar (RE&D)
Kingston, ON, Canada
D-STATCOM · 50 Mvar
Streams62
D-STATCOMValidation
Desert Springs PQ
RE&D Fleet
Riverside, CA
D-STATCOM · 30 Mvar
Streams58
D-STATCOM
Hartford PQ
RE&D Fleet
Hartford, CT
D-STATCOM · 40 Mvar
Streams61
D-STATCOM
Sauk Prairie PQ
RE&D Fleet
Sauk City, WI
D-STATCOM · 25 Mvar
Streams60
D-STATCOMMigration
Longleaf PQ
RE&D Fleet
Tallahassee, FL
D-STATCOM · 35 Mvar
Streams0
D-STATCOMMigration
Foothills PQ
RE&D Fleet
Denver, CO
D-STATCOM · 28 Mvar
Streams59
D-STATCOM
Feeder 52F23 load
SG_A_T2 · phase A
SG_A_T2
T2 winding hot-spot74.00 °C
PM ≤ 45 days
52F22
Breaker timing + contact resistance
52T3
SF6 density + control power
52T2
SF6 density + control power
SG_A_T2.HVAC
HVAC filter + refrigerant
T3
Calisto R9 calibration verification
T1
Calisto R9 calibration verification
Reorder
ABB-HV-BUSHING-72
72 kV condenser bushing (h-j family)
30w lead · 0/3
LS-UVH-38H40E12
LS UVH 38 kV VCB spare pole
26w lead · 1/2
SC-IGBT-MODULE-1200
1200 A IGBT power module
21w lead · 0/2
DOBLE-T1-BTA
Calisto T1 bushing tap adapter
9w lead · 2/6