3

Fleet

Live status across APG's substations and the RE&D power-quality fleet.

Streams
612
Live
Alarms
7
2 critical · 2 warn
Sites healthy
3/7
PM ≤ 30 d
9
Reorder
8
Responder SLA
2 hr
CriticalT2· 22m ago
C₂H₂ rise on T2 — possible arcing in oil

Acetylene climbed from 0.4 ppm → 2.3 ppm over last 14 days. Duval Triangle zone shifted D1 → D2 (high-energy arcing).

Open inbox
Fleet map
7 sites · 1 substation · 6 PQ · click a pin to drill in
EastKingstonDesertHartfordSaukLongleafFoothillsSubstation · normalPQ · warnAlarmOffline
T2 · DGA spotlight
Calisto R9 · Duval zone shifted D1 → D2
CriticalOpen
Acetylene (C₂H₂)
warn 1 · alarm 35 ppm
Hydrogen (H₂)
warn 100 · alarm 500 ppm
CH₄
62.00 ppm
CO
210.00 ppm
Top-oil temp
58.00 °C
Winding hot-spot
74.00 °C

Sites

Substations first · PQ fleet below.

PQ fleet
Feeder 52F23 load
SG_A_T2 · phase A
SG_A_T2
T2 winding hot-spot74.00 °C
PM ≤ 45 days
52F22
Breaker timing + contact resistance
9d overdue
52T3
SF6 density + control power
5d overdue
52T2
SF6 density + control power
1d overdue
SG_A_T2.HVAC
HVAC filter + refrigerant
0d
T3
Calisto R9 calibration verification
2d
T1
Calisto R9 calibration verification
5d
Reorder
ABB-HV-BUSHING-72
72 kV condenser bushing (h-j family)
30w lead · 0/3
Order
LS-UVH-38H40E12
LS UVH 38 kV VCB spare pole
26w lead · 1/2
Order
SC-IGBT-MODULE-1200
1200 A IGBT power module
21w lead · 0/2
Watch
DOBLE-T1-BTA
Calisto T1 bushing tap adapter
9w lead · 2/6
Watch

Command palette

Search assets, alarms, sites, and quick actions

APG Copilot
Hi — I'm your APG assistant. Ask me anything: "any critical alarms?", "draft a DGA report for T2", "what spares are behind their lead time?"

Powered by CopilotKit